Miniature circuit breaker (MCB)

·         A miniature circuit breaker (MCB) automatically switches off the electrical circuits during an abnormal condition of the network in overload condition as well as faulty condition.

·         Thus, it's rating mainly consists of:
1.      Rated current above which it will operated-Available from 0.5A to 63/125A

2    Short circuit current which it can handle-available up to 10-12KA short circuit handling capability
·         The MCB has internal overload and short circuit protection.

·         Quick restoration of supply is possible in case of MCB as compare to the fuse where we need to rewire it after each operation.

1.1.            Working Principle of MCB

Figure: Different parts of MCB

1.      If the circuit is overloaded for some prescribed time, the bimetallic strip becomes overheated and deformed. This deformation of bimetallic strip causes, displacement of tripping lever.
The displacement of the tripping lever causes the release of spring and makes the moving contact to move for opening the MCB.
2.       In the case of a short circuit, the MMF produces in the electromagnetic coil causes plunger to hit the tripping lever, resulting in the release of spring to open the MCB. The arc produced due to short circuits has been quenched in the arc chamber by lengthening the arc principle.

1.2.            Selection Of MCB

Following points are taken into consideration while selecting MCB:
  • Rated Current-0.5 to 63A/125A
  • Short circuit current- The maximum short circuit current can interrupt safely. It is Up to 10 to 12kA
  •  Operating voltage-System or equipment voltage. Generally, 230V/415V
  •   Frequency-50/60Hz
  •   Trip curve characteristics-Tripping current is the minimum current at which The MCB will trip instantaneously.
MCB Type
Tripping Current
Trip Curve class B
Above 3 to 5 times rated current. Suitable for cable protection
Trip Curve class C
Above 5 to 10 times the rated current. Suitable Domestic and residential applications and electromagnetic starting loads with medium starting currents
Trip Curve class D
More than 10 to 20 times. Suitable for inductive and motor load with high starting
Trip Curve class K
Above 8 to 12 times the rated current. Suitable for inductive and motor loads with high inrush currents
Trip Curve class Z
Above 2 to 3 times the rated current. These type of MCBs are highly sensitive to short circuit and are used for the protection of highly sensitive devices such as semiconductor devices.

Figure: Nameplate details of 50A MCB

1.3.            Selection of MCB  current rating



MCB rated current=1.25*Full load current
The IEC standard for CB is 60947-1/2 or IS 13947