- MCCB is a device that is used for protection against overload and electrical fault and to switch ON/OFF the circuit. Thus, they have inherent overload and short circuit protection.
- The main difference between Miniature circuit breaker and the Molded case circuit breaker is that the MCCB is designed for higher fault current ratings and the adjustable trip setting is provided which is not available in case of MCB’S.
- They are rated from 63 to 630A and have short circuit withstand capability up to 50KA/s
I.
RATINGS OF MCCB
Figure 1:The rating parameters of MCCB
A. Rated current (100A in this case): The Service current above which the overload protection trips the
MCCB.
B. Rated Insulation Voltage (Ui): The maximum voltage
that the MCCB can resist according to laboratory tests. To provide a safety
margin, this is higher than the rated working voltage.
C.Rated
operational Voltage (Ue): The
continuous operating voltage for which the MCCB is designed. Generally, it is
equal to or close to system voltage
D.Rated
Impulse withstand voltage (Vimp): The value of voltage which the equipment is
capable of withstanding without failure, under test conditions.
(Generally, 8KV for industrial and 6 kV for domestic type)
E.Rated
service short circuit breaking capacity (Ics): The highest fault
current that the MCCB can trip without being damaged permanently. The MCCB will
be reusable after interrupting a fault, as long as it doesn’t exceed this value.
F.Rated
ultimate short-circuit breaking capacity (Icu): The maximum
possible fault current that the MCCB can clear. If the fault current exceeds
this value, the MCCB will be unable to trip and another protection mechanism
with a higher breaking capacity must operate. If a fault above the Ics but
below the Icu occurs, the MCCB can interrupt it
successfully but will most likely need a replacement due to the damage
suffered.
G. Adjustment
dial for the magnetic protection pickup Im:
To adjust the current rating as per circuit current.
II.
SIZING OF MCCB
Following points should be carefully taken into
consideration while sizing the MCCB
1. The rated working voltage of the MCCB must match the system voltage of the application. e,.g 415.
2.The MCCB must
be adjustable to the adequate trip value, calculated according to the current drawn by the load.
3. The operating breaking capacity of the MCCB must be higher than the expected fault currents in the system.
III. FRAME SIZE RATING
Example: For 50kW,3phase ,415V 0.9
power factor continuous load with 18KA fault current in the circuit, full load the current of load can be calculated as:
I Ifl =(50)/(1.732*415*0.9) =77.29Amps
Thus the rating of MCCB will be:
= 1.25*Full load current=1.25*77.29=96.61
Next available standard higher
rating of MCCB is 100A
Thus 100 Amps MCCB with 20KA fault current rating will be chosen.
Figure 2:Trip relay setting of MCCB
- The circuit breaker can be equipped with electronic trip units to adjust the tripping current. Overload relay trip-current setting (Irth or Ir). Apart from small circuit breakers which are very easily replaced, industrial circuit breakers are equipped with removable, i.e. exchangeable, overcurrent-trip relays. Moreover, in order to adapt a circuit breaker to the requirements of the circuit it controls, and to avoid the need to install over-sized cables, the trip relays are generally adjustable.
- The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit breaker will trip. It also represents the maximum current that the circuit breaker can carry without tripping.
- That value must be greater than the maximum load current IL, but less than the maximum current permitted in the circuit
- The thermal-trip relays are generally adjustable from 0.7 to 1.0 times In, but when electronic devices are used for this duty, the adjustment range is greater; typically 0.4 to 1 times In.
- As shown in the diagram, a circuit breaker equipped with an overcurrent trip relay, set at 0.9, will have a trip-current setting:Ir = 300 x 0.9 = 270 A