Miniature
circuit breaker (MCB)
·
A miniature circuit breaker (MCB) automatically
switches off the electrical circuits during an abnormal condition of the network in overload condition as well as faulty condition.
·
Thus, it's rating mainly consists of:
1.
Rated current above which it will operated-Available from 0.5A to 63/125A
2 Short circuit current which it can handle-available up to 10-12KA short
circuit handling capability
·
The MCB has internal overload and short circuit
protection.
·
Quick restoration of supply is possible in case
of MCB as compare to the fuse where we need to rewire it after each operation.
1.1.
Working Principle of MCB
Figure: Different parts of MCB
1.
If the circuit is overloaded for some
prescribed time, the bimetallic strip becomes overheated and deformed. This
deformation of bimetallic strip causes, displacement of tripping lever.
The
displacement of the tripping lever causes the release of spring and makes the moving contact
to move for opening the MCB.
2.
In the case of a short circuit, the MMF produces in the electromagnetic coil causes plunger to hit the tripping lever, resulting in the release of spring to open the MCB. The arc produced due to short circuits has
been quenched in the arc chamber by lengthening the arc principle.
1.2.
Selection Of
MCB
Following
points are taken into consideration while selecting MCB:
- Rated Current-0.5 to 63A/125A
- Short circuit current- The maximum short circuit current can interrupt safely. It is Up to 10 to 12kA
- Operating voltage-System or equipment voltage. Generally, 230V/415V
- Frequency-50/60Hz
- Trip curve characteristics-Tripping current is the minimum current at which The MCB will trip instantaneously.
|
MCB Type
|
Tripping Current
|
|
Trip Curve class B
|
Above 3 to 5 times rated current. Suitable for cable protection
|
|
Trip Curve class C
|
Above 5 to 10 times the rated current. Suitable Domestic and
residential applications and electromagnetic starting loads with medium
starting currents
|
|
Trip Curve class D
|
More than 10 to 20 times. Suitable for inductive and motor load with
high starting
|
|
Trip Curve class K
|
Above 8 to 12 times the rated current. Suitable for inductive and
motor loads with high inrush currents
|
|
Trip Curve class Z
|
Above 2 to 3 times the rated current. These type of MCBs are highly
sensitive to short circuit and are used for the protection of highly
sensitive devices such as semiconductor devices.
|

Figure: Nameplate details of 50A MCB
1.3.
Selection of MCB current rating
MCB rated current=1.25*Full load current
The IEC
standard for CB is 60947-1/2 or IS 13947